Application Guide - NP900 Series
385 (504
)
A996A
Object registers are treated different from other registers seen in the IED. Following
example is from closing of the breaker when the breaker is not ready.
dd.mm.yyyy hh:mm:ss.mss ObjectOpen, WDIn, Close request from RemCloInput,Close pending due to:
Close wait for Ready, Open Allowed, Close Allowed, Object Not Ready
dd.mm.yyyy hh:mm:ss.mss ObjectOpen,WDIn,Open Allowed,Close Allowed,ObjectReady
dd.mm.yyyy hh:mm:ss.mss ObjectClosed,WDIn,Open Allowed,Close Allowed,ObjectReady,Obj
closetime:0.070s
Corresponding event list is as below
dd.mm.yyyy hh:mm:ss.mss
CloseRequestOn
dd.mm.yyyy hh:mm:ss.mss
CloseFail
dd.mm.yyyy hh:mm:ss.mss
CloseRequestOff
dd.mm.yyyy hh:mm:ss.mss
CloseCommandOn
dd.mm.yyyy hh:mm:ss.mss
StatusChangedOn
dd.mm.yyyy hh:mm:ss.mss
ObjectIntermediate
dd.mm.yyyy hh:mm:ss.mss
ObjectClose
dd.mm.yyyy hh:mm:ss.mss
CloseCommandOff
As can be seen the registers complement the event list information in cases when the
control has failed. The reason of failure can be seen directly from the registers
3.6.3
S
YNCHRO
-
CHECK FUNCTION
Δ
F
,
ΔU,
Δ
Φ
To ensure safe closing of the circuit breaker between two systems it is important to check
the synchronization. Closing the circuit breaker while the systems are in asynchronous
state can cause several problems like current surges which damage the interconnecting
elements. Synchrocheck has three stages SYN1, SYN2 and SYN3. SYN1 supervises the
synchronization condition between U4 channel and the selected input voltage. SYN2
supervises the synchronization condition between U3 channel and the selected input
voltage. SYN3 supervises the synchronization condition between U3 and U4 channels.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...