Application Guide - NP900 Series
346 (504
)
A996A
Figure 1.1.1.8-163 Inrush blocking by using 2
nd
harmonic related to fundamental
frequency component.
Figure 1.1.1.8-164 Example of transformer magnetizing inrush currents.
As conservative setting suggestion for standard type transformer could be recommended
2
nd
harmonic blocking enabled with sensitivity set to around 15-20% harmonic content
compared to fundamental frequency. Final tuning for the transformer settings can be
made in commissioning if there should be any issues on problematic transformer
energisation.