Autoreclosing Reclaim Time is exceeded and Autorecloser is set to Ready state
waiting for next request.
3.6.4.5
A
UTORECLOSING SEQUENCE FROM
T
RIP WITH TWO SHOT
,
HIGH SPEED
SUCCEEDS
The Scheme for autoreclosing starter and shots is the same than in the previous
examples with same settings and signals. In this example fault is cleared by the high
speed autoreclosing.
Figure 3.6.4.5-188 Settings for earth fault reclosing with two shots.
This type of sequence represents 75-85% of all the faults in the medium voltage overhead
line network.