Application Guide - NP900 Series
77 (504
)
A996A
measurement input I01
I02PP
Peak-to-peak measurement of sensitive residual current
measurement input I02
5 ms
I02RMS
Fundamental RMS measurement of sensitive residual
current measurement input I02
5 ms
I02TRMS
TRMS measurement of coarse sensitive current
measurement input I02
5 ms
I0Calc
Fundamental RMS value of the calculated residual current
from the three phase currents
5 ms
U0RMS
Fundamental RMS measurement of zero sequence voltage
measurement input U0
5 ms
U0Calc
Fundamental RMS value of the calculated zero sequence
voltage from the three phase voltages
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input
channel variations pre-fault condition is presented with 20 ms averaged history value from
-20 ms of Start or Trip event.
3.2.5.2
P
ICK
-
UP CHARACTERISTICS
Pick-up of the DEF function is controlled by
I0set
setting parameter, which defines the
maximum allowed measured current, U0set setting parameter which defines the
maximum allowed measured voltage and checks the angle difference before action from
the function. The function constantly calculates the ratio in between of the Iset/Uset and
measured magnitudes (Im/Um). Reset ratio of 97 % is inbuilt in the function and is always
related to the
I0set
value (or U0set). Im exceed of the I0set value will cause pick-up
operation of the function.
Table 3.2.5.2-60 Pick-up characteristics setting
Name
Description
Range
Step
Default
I0set
Pick-up setting
0.01 … 40.00 x In
0.001 x In
1.20 x In
U0set
Pick-up setting
1…75 %Un
0.01 (%Un)
20 %Un
Grounding
type
Network
grounding
method
1.
Unearthed
2.
Petersen coil grounded
3.
Grounded network
-
Unearthed
Angle
Trip area size
(Grounded
network)
±45.0…135.0°
0.1°
±88°
Angle offset
Protection area
direction
(Grounded
0.0…360.0°
0.1°
0.0°
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...