Application Guide - NP900 Series
72 (504
)
A996A
value. The setting value is common for all measured phases and single-, dual- or all
phases Im exceed of the Iset value will cause pick-up operation of the function.
The fault has to be in the monitored direction as well to fulfill the terms to trip. Fault
direction can be set to forward or reverse. Tripping area is ±88° (176°) and reference
angle is based on calculated positive sequence voltage U1 angle. In case U1 voltage is
not available and only line to line voltages are measured the angle reference is based on
healthy line to line voltage and during short circuit to impedance calculation. If voltage
drops below 1V secondary the angle memory is used for 0.5 seconds. Angle memory
forces the angle reference to the value that was measured or calculated before the fault.
Angle memory captures the measured voltage angle 100 ms before the fault starts. After
0.5 seconds the angle memory is not used anymore and reference voltage is forced to 0°.
Inbuilt reset ratio for the trip area angle is 2.
Table 3.2.4.3-56 Pick-up characteristics setting
Name
Description
Range
Step
Default
Iset
Pick-up setting
0.10 … 40.00 x In
0.01 x In
1.20 x In
Center
Pick-up center
-180.0…180.0°
0.1°
0°
Angle
Pick-up area
±1.0…170.0°
0.1°
±88°
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active.
Figure 3.2.4.3-37 Angle tracking of DOC function (3LN or 3LL+U0 mode).
U1
I1
I1
U1
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...