Application Guide - NP900 Series
393 (504
)
A996A
1.1.1.13
F
UNCTION BLOCKING
In the blocking element the block signal is checked in the beginning of each program
cycle. Blocking signal is received from the blocking matrix for the function dedicated input.
If the blocking signal is not activated when the synchronization is ok, a SYN OK signal is
generated.
If blocking signal is active when SYN OK activates a BLOCKED signal will be generated
and the function shall not process the situation further. If SYN OK function has been
activated before blocking signal it will reset.
From blocking of the function a HMI display event as well as time stamped blocking event
with information of the startup voltage values and fault type is issued.
Blocking signal can be tested also in the commissioning phase of the stage by software
switch signal when relay common and global testing mode is activated. User settable
variables are binary signals from the system.
1.1.1.14
S
ETTING PARAMETERS
Table 1.1.1.14-242 General settings of the synchrocheck function
Name
Range
Step
Default
Description
Use SYN1,2,3
No
Yes
-
No
Activation of individual stages of the
synchrocheck function. Activation of a
stage reveals the parameter settings for
configuration.
SYN1 (U4) V
Reference
Not in use
UL12
UL23
UL31
UL1
UL2
UL3
-
Not in use
- Choose the reference voltage of the
stage.
- In 3LN+U4 and 2LL+U0+U4 mode all
references are available.
- In 3LL+U4 and 2LL+U3+U4 mode UL12,
UL23 and UL31 references are available
SYN2 (U3) V
Reference
Not in use
UL12
UL23
UL31
UL1
UL2
UL3
-
Not in use
- Choose the reference voltage of the
stage.
- In 2LL+U3+U0 mode all references are
available
- In 2LL+U3+U4 mode UL12, UL23 and
UL31 are available
SYN3 Reference
Not in use
U3-U4
-
Not in use
- Choose if SYN3 stage is activated or
disabled
- Operable in 2LL+U3+U4 mode
- UL12, UL23 and UL31 references are
available
Table 1.1.1.14-243 Synchrocheck stage settings
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...