Application Guide - NP900 Series
66 (504
)
A996A
Table 3.2.3.1-51 Analogic magnitudes used by the NEF function.
Signal
Description
Time base
I01PP
Peak-to-peak measurement of coarse residual current
measurement input I01
5 ms
I01RMS
Fundamental RMS measurement of coarse residual current
measurement input I01
5 ms
I01TRMS
TRMS measurement of coarse residual current
measurement input I01
5 ms
I02PP
Peak-to-peak measurement of sensitive residual current
measurement input I02
5 ms
I02RMS
Fundamental RMS measurement of sensitive residual
current measurement input I02
5 ms
I02TRMS
TRMS measurement of coarse sensitive current
measurement input I02
5 ms
I0Calc
Fundamental RMS value of the calculated zero sequence
current from the three phase currents
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input
channel variations pre-fault condition is presented with 20 ms averaged history value from
-20 ms of Start or Trip event.
3.2.3.2
P
ICK
-
UP CHARACTERISTICS
Pick-up of the NEF function is controlled by
I0set
setting parameter, which defines the
maximum allowed measured current before action from the function. The function
constantly calculates the ratio in between of the Iset and measured magnitude (Im) per all
three phases. Reset ratio of 97 % is inbuilt in the function and is always related to the
Iset
value. The setting value is common for all measured phases and single-, dual- or all
phases Im exceed of the Iset value will cause pick-up operation of the function.
Table 3.2.3.2-52 Pick-up characteristics setting
Name
Description
Range
Step
Default
I0set
Pick-up setting
0.005 … 40.00 x In
0.001 x In 1.20 x In
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...