Application Guide - NP900 Series
47 (504
)
A996A
Delay curve series IEC
IEEE
-
IEC
Setting is active and visible when Delay
Type is selected to IDMT.
Delay curve series for IDMT operation
following either IEC or IEEE/ANSI
standard defined characteristics.
Delay
characteristics
IEC
NI
EI
VI
LTI
Param
-
NI
Setting is active and visible when Delay
Type is selected to IDMT.
IEC standard delay characteristics.
Normally Inverse, Extremely Inverse, Very
Inverse and Long Time Inverse
characteristics. Param selection allows the
tuning of the constants A and B which
allows setting of characteristics following
the same formula as the IEC curves
mentioned here.
Delay
characteristics
IEEE
ANSI NI
ANSI VI
ANSI EI
ANSI LI
IEEE MI
IEEE VI
IEEE EI
Param
-
LTI
Setting is active and visible when Delay
Type is selected to IDMT.
IEEE and ANSI standard delay
characteristics. ANSI: Normal Inverse,
Very Inverse, Extremely inverse, Long
time inverse characteristics. IEEE:
Moderately Inverse, Very Inverse,
Extremely Inverse characteristics. Param
selection allows the tuning of the
constants A, B and C which allows setting
of characteristics following the same
formula as the IEEE curves mentioned
here.
Time dial setting k 0.01…25.00 s
0.01 s
0.05 s
Setting is active and visible when Delay
Type is selected to IDMT.
Time dial / multiplier setting for IDMT
characteristics.
A
0.0000…250.0000
0.0001
0.0860
Setting is active and visible when Delay
Type is selected to IDMT.
Constant A for IEC/IEEE characteristics.
B
0.0000…5.0000
0.0001
0.1850
Setting is active and visible when Delay
Type is selected to IDMT.
Constant B for IEC/IEEE characteristics.
C
0.0000…250.0000
0.0001
0.0200
Setting is active and visible when Delay
Type is selected to IDMT.
Constant C for IEEE characteristics.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...