Application Guide - NP900 Series
192 (504
)
A996A
Figure 3.2.20-96 Simplified function block diagram of the RPW function.
3.2.20.1
M
EASURED INPUT VALUES
Three phase active power value is used for the function block. For pre-fault data
registering is used -20ms averaged value.
Table 3.2.20.1-133 Measurement magnitudes used by the RPW function.
Signal
Description
Time base
3PH Active power (P)
Total 3 phase active power
5 ms
3.2.20.2
P
ICK
-
UP CHARACTERISTICS
Pick-up of the RPW function is controlled by
Pset rev.
setting parameter, which defines
the maximum allowed measured three phase active power before action from the function.
The function constantly calculates the ratio in between of the Pset rev. and measured
magnitude (Pm). Reset ratio of 97 % is inbuilt in the function and is always related to the
Pset rev.
value.
Table 3.2.20.2-134 Pick-up characteristics setting
Name
Description
Range
Step
Default
Pset rev.
Pick-up setting
0.0…100000 kW 0.01 kW
100 kW
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...