Application Guide - NP900 Series
125 (504
)
A996A
Figure 3.2.10.3-64 Restricted earth fault on inside of Y winding transformer.
3.2.10.4
E
VENTS AND REGISTERS
The REF function generates events and registers from the status changes of the Trip
activated and blocked signals. To main event buffer is possible to select status “On” or
“Off” messages.
In the function is available 12 last registers where the triggering event of the function (Trip
activated or blocked) is recorded with time stamp and process data values.
Table 3.2.10.4-88. Event codes of the REF function instance
In the register of the REF function is recorded activated, blocked etc. “On” event process
data. In the table below is presented the structure of REF function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.10.4-89. Register content.
Date & Time
Event
code
Trigger currents
Trigger currents
Residual
currents
Used SG
dd.mm.yyyy
hh:mm:ss.mss
4224-
4227
Descr.
Biascurrent trig
Diffcurrent trig
Characteristics
diff trig
Biascurrent max
Diffcurrent max
Characteristics diff
max
I0Calc
I0 meas
1 - 8
0.00
1.00
2.00
0
1
2
3
4
5
6
7
I D
if
f
I Bias
Differential characteristics
Characteristics
DIFF
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
4224
66 REF1
0 REF Trip On
1
4225
66 REF1
1 REF Trip Off
0
4226
66 REF1
2 REF Block On
1
4227
66 REF1
3 REF Block Off
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...