Application Guide - NP900 Series
148 (504
)
A996A
Table 3.2.12.3-101 Enabled Zone pick-up characteristics setting
Name
Description
Phase current pick-up
Phase current measurement pick-up value in per-
unit value.
I0 input selection
Selection of the residual current channel between
I01 and I02
Res.current pick-up
Residual current measurement pick-up value in
per-unit value.
Zone Ph. Curr Enabled
Phase overcurrent allows the zone to trip when
light is detected
Zone Res.Curr Enabled
Residual overcurrent allows the zone to trip when
light is detected
Zone Light 1 Enabled
Light detected in sensor channel 1 trips the zone
Zone Light 2 Enabled
Light detected in sensor channel 2 trips the zone
Zone Light 3 Enabled
Light detected in sensor channel 3 trips the zone
Zone Light 4 Enabled
Light detected in sensor channel 4 trips the zone
The pick-up activation of the function is not directly equal to trip-signal generation of the
function. Trip signal is allowed if blocking condition is not active.
3.2.12.4
F
UNCTION BLOCKING
In the blocking element the block signal is checked at the beginning of each program
cycle. Blocking signal is received from the blocking matrix for the function dedicated input.
If the blocking signal is not activated when the pick-up element activates, a TRIP signal is
generated and the function proceeds to the time characteristics calculation.
If blocking signal is active when pick-up element activates a BLOCKED signal will be
generated and the function shall not process the situation further. If TRIP function has
been activated before blocking signal it will reset and the release time characteristics are
processed as in case of when pick-up signal is reset.
From blocking of the function an HMI display event as well as time stamped blocking
event with information of the startup voltage values and fault type is issued.
Blocking signal can be tested also in the commissioning phase of the stage by software
switch signal when relay common and global testing mode is activated.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...