Table 3.6.4.12-245 AR input signals.
Signal
Range
Description
AR
spontaneous
blocking
Any binary
signal in the
IED
Input for dynamically block the autoreclosing. When input is activated
the recloser will halt its operation and refuses any further requests.
When signal is released recloser will continue its operation as were
before receiving this signal.
AR manual
reset
Any binary
signal in the
IED
Input for resetting the recloser manually in case it is locked due to final
trip or any other possible cause for locking.
AR Locking
Any binary
signal in the
IED
Locking of the autorecloser so that it needs manual reset before its
operation is allowed to be set ready.
AR1 Request
Any binary
signal in the
IED
Reclosing request 1, highest priority request which overrules all lower
priority requests for autoreclosing. When this request signal is activated
and other conditions for reclosing are met a shot will be applied.
AR2 Request
Any binary
signal in the
IED
Reclosing request 2, second highest priority request which overrules all
lower priority requests for autoreclosing. When this request signal is
activated and other conditions for reclosing are met a shot will be
applied.
AR3 Request
Any binary
signal in the
IED
Reclosing request 3, third highest priority request which overrules all
lower priority requests for autoreclosing. When this request signal is
activated and other conditions for reclosing are met a shot will be
applied.
AR4 Request
Any binary
signal in the
IED
Reclosing request 4, fourth highest priority request which overrules all
lower priority requests for autoreclosing. When this request signal is
activated and other conditions for reclosing are met a shot will be
applied.
AR5 Request
Any binary
signal in the
IED
Reclosing request 5, lowest priority request which overrules all lower
priority requests for autoreclosing. When this request signal is activated
and other conditions for reclosing are met a shot will be applied.
Critical
Request
Any binary
signal in the
IED
Critical request for autoreclosing, if this signal is activated the
autorecloser shall go directly to locked state and trip the breaker directly
in the moment the request was received.
Status change of the input signals will always cause recorded event also in the object
registers and object continuous status indications. Events can be enabled or disabled
according to the application requirements.
3.6.4.13
O
UTPUT SIGNALS OF AUTORECLOSER
Output functions of the autorecloser in this mean are indication signals only. The breaker
open and close commands are controlled by object function.
Table 3.6.4.13-246 AR output signals.
Signal
Description
AR Running
When autorecloser is in running mode this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
AR1 Request On
When autorecloser is executing shot requested by AR1 priority this signal is
activated. Signal can be connected to any relay IO as well as into communication
protocols.
AR2 Request On
When autorecloser is executing shot requested by AR2 priority this signal is
activated. Signal can be connected to any relay IO as well as into communication
protocols.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...