Application Guide - NP900 Series
464 (504
)
A996A
Table 3.7.1.2-273 Pick-up characteristics setting
Name
Range
Step
Default
Description
Iset Highlimit 0.01 … 40.00 x In
0.01 x In
1.20 x In
Pick-up threshold for phase current
measurement. This setting limit defines the
upper limit for the phase current pick-up
element. If this condition is met it is
considered as fault and the CTS is not
activated
Iset Lowlimit 0.01 … 40.00 x In
0.01 x In
0.10 x In
Pick-up threshold for phase current
measurement. This setting limit defines the
lower limit for the phase current pick-up
element. If this condition is met it is
considered as one trigger for the CTS
activation.
Iset Ratio
0.01 … 100.00 %
0.01 %
10.00 %
Pick-up ratio threshold for phase current
min and max values. This condition has to
be met in order CTS is activated.
I2/I1 ratio
0.01 … 100.00 %
0.01 %
49.00 %
Pick-up ratio threshold for Negative
sequence / Positive sequence currents
calculated from the phase currents. This
condition has to be met in order CTS is
activated. In full single phasing fault when
one of the phases is completely lost the
ratio shall be 50%. Setting of 49% allows
0.01 xIn to flow in one phase when the two
other are 1.00 xIn
Isum
difference
0.01 … 40.00 x In
0.01 x In
0.10 x In
Pick-up ratio threshold for calculated
residual phase current to measured
residual current. If the measurement circuit
is healthy the sum of these should be 0.
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active. From binary signals the
activation of the pick-up is immediate when the monitored signal is activated.
3.7.1.3
F
UNCTION BLOCKING
In the blocking element the block signal is checked in the beginning of each program
cycle. Blocking signal is received from the blocking matrix for the function dedicated input.
If the blocking signal is not activated when the pick-up element activates, a START signal
is generated and the function proceeds to the time characteristics calculation.
If blocking signal is active when pick-up element activates a BLOCKED signal will be
generated and the function shall not process the situation further. If START function has
been activated before blocking signal it will reset and the release time characteristics are
processed as in case of when pick-up signal is reset.
From blocking of the function a HMI display event as well as time stamped blocking event
with information of the startup current values and fault type is issued.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...