Application Guide - NP900 Series
312 (504
)
A996A
Table 1.1.1.1-208. Output signals of the TRF function
Name
Range
Step
Default
Description
No/Light load
0=Not active
1=Active
1
0
Signal is active, when the TRF function
detects current below “No load current”.
This signal presents situation when there is
very light load or only one or neither side of
trafo is energized.
HV side inrush
detected
0=Not active
1=Active
1
0
Signal is active, when the detected current
rises over the “High overcurrent” limit in the
HV side.
LV side inrush
detected
0=Not active
1=Active
1
0
Signal is active, when the detected current
rises over the “High overcurrent” limit in the
LV side.
Load normal
0=Not active
1=Active
1
0
Signal is active when the measured current
is below nominal and over no load limit
current.
Overloading
0=Not active
1=Active
1
0
Signal is active when the measured current
is in between nominal and high overcurrent
limits.
HVY Overloading 0=Not active
1=Active
1
0
Signal is active when the measured current
is over high overcurrent limit.
1.1.1.2
E
VENTS
TRF function generates events from detected transformer energizing status. From
changes of the events also data register is available.
Table 1.1.1.2-209. Event codes of the TRF function.
Event
Number
Event
channel
Event block name
Event
Code
Description
4608
72 TRF1
0 Light/No load On
4609
72 TRF1
1 Light/No load Off
4610
72 TRF1
2 HV side inrush On
4611
72 TRF1
3 HV side inrush Off
4612
72 TRF1
4 LV side inrush On
4613
72 TRF1
5 LV side inrush Off
4614
72 TRF1
6 Load normal On
4615
72 TRF1
7 Load normal Off
4616
72 TRF1
8 Overloading On
4617
72 TRF1
9 Overloading Off
4618
72 TRF1
10 High overload On
4619
72 TRF1
11 High overload Off
4620
72 TRF1
12 Setting changes, calculating new trafo data
4621
72 TRF1
13 Calculation finished, possible restart
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...