Application Guide - NP900 Series
439 (504
)
A996A
3.6.7.1
AVR
FEATURES AND CONFIGURATION
AVR features separate definite and inverse operating time voltage raise and lower
windows, instant overvoltage lower, undervoltage blocking and inbuilt overcurrent blocking
functions. Target voltage as well as operating settings for the voltage windows can be
changed via setting group changes. Tap changer location is monitored with mA
measurement. Tap changer position can be controlled with automatic control and manual
control. AVR monitors bus phase to phase voltage. Operation of the AVR can be blocked
by external commands by blocking either control algorithm completely or blocking the
control outputs only.
Configuring of the AVR is presented in following examples.
General settings
General settings include the measurement reference voltage selection. In this part the
measured phase to phase voltage has to be selected as well as the measurement input in
case if U4 input is used for voltage measurements.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...