Application Guide - NP900 Series
71 (504
)
A996A
Table 3.2.4.1-55 Analogic magnitudes used by the DOC function.
Signal
Description
Time base
IL1PP
Peak-to-peak measurement of phase L1/A current
5 ms
IL2PP
Peak-to-peak measurement of phase L2/B current
5 ms
IL3PP
Peak-to-peak measurement of phase L3/C current
5 ms
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
IL1TRMS
TRMS measurement of phase L1/A current
5 ms
IL2TRMS
TRMS measurement of phase L2/B current
5 ms
IL3TRMS
TRMS measurement of phase L3/C current
5 ms
U
1
RMS
Fundamental RMS measurement of voltage U
1
/V
5 ms
U
2
RMS
Fundamental RMS measurement of voltage U
2
/V
5 ms
U
3
RMS
Fundamental RMS measurement of voltage U
3
/V
5 ms
U
4
RMS
Fundamental RMS measurement of voltage U
4
/V
5 ms
Selection of the used current AI channel is made with a setting parameter. In all possible
input channel variations pre-fault condition is presented with 20 ms averaged history value
from -20 ms of Start or Trip event.
3.2.4.2
R
EAL
-
TIME INFO DISPLAYED OF THE FUNCTION
The relays Info-page displays useful information in real time of the state of the protection
function either through relays HMI display or with SMART9 software when connection
there is a connection to relay and Live Edit-mode is activated.
Name
Unit
Description
Operating angle now
Deg
Positive sequence current angle in relation to positive
sequence voltage
Expected operating time
s
Displays the expected operating time in case a fault
occurs
Time remaining to trip
s
When the relay has picked up and is counting time
towards pick-up
Imeas/Iset at the moment
Im/Iset
Ratio between positive sequence current and the pick-
up value.
3.2.4.3
P
ICK
-
UP CHARACTERISTICS
Pick-up of the DOC function is controlled by
Iset
setting parameter, which defines the
maximum allowed measured current before action from the function. The function
constantly calculates the ratio in between of the Iset and measured magnitude (Im) per all
three phases. Reset ratio of 97 % is inbuilt in the function and is always related to the
Iset
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...