Application Guide - NP900 Series
262 (504
)
A996A
I< (37)
Im> (50M)
Nominal starting
current
0.1…40.0XIn 0.1xIn 6.0 xIn
MST
TM> (49M)
Ist> (48)
Im> (50M)
Motors locked rotor current with
nominal voltage. This setting is used
for the automatic curve selection
and calculation. Also nominal
starting capacity calculation is made
with this value.
Nominal starting
current A
0.1 ... 5000A 0.1A
-
MST
TM> (49M)
Ist> (48)
Im> (50M)
Motors locked rotor current in
amperes.
Start detect
current
0.1…40.0xIn 0.1xIn 1.5 xIn
MST
Ist> (48)
Motor starting current detection
limit. When in DOL or Start delta
mode this setting defines the
starting situation when measured
current exceeds this and no load
current setting in 10 ms time.
Start detect
current A
0.1 ... 5000A 0.1A
-
MST
Ist> (48)
Motor starting current detection limit
in amperes.
Min locked rotor
current
0.1…40.0xIn 0.1xIn 3.5 xIn
MST
TM> (49M)
Ist> (48)
Im> (50M)
Minimum locked rotor current of the
motor. This setting defines the
current limit when in the automatic
curve selection and control only
short time constant (stall) is used if
this current is exceeded.
Min locked rotor
current A
0.1 ... 5000A 0.1A
-
MST
TM> (49M)
Ist> (48)
Im> (50M)
Minimum locked rotor current of the
motor. This setting defines the
current limit when in the automatic
curve selection and control only
short time constant (stall) is used if
this current is exceeded.
Max locked rotor
current
0.1…40.0xIn 0.1xIn 7.5 xIn
MST
TM> (49M)
Ist> (48)
Im> (50M)
Maximum locked rotor current of the
motor. This setting defines the
current limit which is maximum
current for the motor to draw in
locked rotor situation (starting or
stalled). If the measured current
exceeds this setting limit it is
considered to be overcurrent fault
and corresponding measures can
be applied to disconnect the feeder
and motor from the supply.
Max locked rotor
current A
0.1 ... 5000A 0.1A
-
MST
TM> (49M)
Ist> (48)
Im> (50M)
Maximum locked rotor current in
amperes.
Max overload
current
0.1…40.0xIn 0.1xIn 2.0 xIn
MST
TM> (49M)
Ist> (48)
Im> (50M)
Max overload current of the motor.
Over this setting motor is stalled.
This setting defines when the
thermal replica switches to short
(stall) time constant if exceeded.
Under this setting value the motor
should be running still even
overloaded.
Max overload
current A
0.1 ... 5000A 0.1A
-
MST
TM> (49M)
Ist> (48)
Im> (50M)
Max overload current of the motor in
amperes.
Hot condition
theta limit
0.0…100.0% 0.1% 70%
MST
N> (48)
Setting of the thermal limit Hot /
Cold situation of the motor. When
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...