Application Guide - NP900 Series
273 (504
)
A996A
From blocking of the function a HMI display event as well as time stamped blocking event
with information of the startup current values and fault type is issued.
Blocking signal can be tested also in the commissioning phase of the stage by software
switch signal when relay common and global testing mode is activated.
User settable variables are binary signals from the system. Blocking signal needs to reach
the IED minimum of 5 ms before the set operating delay has passed for blocking to be
active in time.
3.3.5.5
E
VENTS AND REGISTERS
The NUC function generates events and registers from the status changes of start, trip
and blocked. To main event buffer is possible to select status “On” or “Off” messages. The
NUC function offers four independent instances which events are segregated for each
instance operation.
In the function is available 12 last registers where the triggering event of the function
(start, trip or blocked) is recorded with time stamp and process data values.
Table 3.3.5.5-175. Event codes of the NUC function
In the register of the NUC function is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of NUC function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.3.5.5-176. Register content.
Date & Time
Event
code
Fault
type
Trigger
current
Fault
current
Prefault
current
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
3840-
3845
Descr.
L1-G…
L1-L2-
L3
Start
average
current
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
3840
60 NUC1
0 Start ON
1
3841
60 NUC1
1 Start OFF
0
3842
60 NUC1
2 Trip ON
1
3843
60 NUC1
3 Trip OFF
0
3844
60 NUC1
4 Block ON
1
3845
60 NUC1
5 Block OFF
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...