Application Guide - NP900 Series
400 (504
)
A996A
3.6.4.3
A
UTORECLOSING SEQUENCE FROM
T
RIP WITH TWO SHOT FAILURE
For this earth fault autoreclosing scheme directional earth fault protection Trip signal to
operate was set as REQ2 starter which was enabled to Shot1 and Shot2 with following
settings. One rapid shot followed by time delayed shot is set for this scheme.
Figure 3.6.4.3-184 Settings for earth fault reclosing with two shots.
When Trip signal is used for the autorecloser cycle init then no additional starting or
discrimination times are used since the protection stage takes care of the breaker opening
timings directly by its own operation. Autorecloser therefore only monitors the status of the
directional earth fault stage tripping before initiating request and shots.
Figure 3.6.4.3-185 Signal status graph of the permanent earth fault autoreclosing cycle.