Application Guide - NP900 Series
250 (504
)
A996A
(This setting is visible when “multiple”
time constants is selected and also
“Set manual” is selected for the
“Estimate short TC and timings”).
Wf factor for L/S T const
0.0…1.0
0.1
0.5
Weighting factor in between of the
currently used long and short time
constants. With this setting the
heating/cooling calculation can be fine
tuned. Setting value 0.5 means that
50% of the heating or cooling is
calculated based into long time
constant and 50% based into short
time constant. 0.0 means 100% short
time constant and 1.0 means 100%
long time constant. (This setting value
is visible when “multiple” time
constants is selected).
T const dyn. balancing
0:Fixed
1:Dynamic
-
0:Fixed
Selection whether the thermal replica
balances and switches the time
constants dynamically based into the
detected motor status. Switching is
based into the settings given for
maximum overload current and
minimum locked rotor current. With
selection “Dynamic” the thermal
replica switches the timeconstants
and with setting “Fixed” no time
constants are switched. (This setting
value is visible when “multiple” time
constants is selected).
Short Cool T used when
stop
0.0...3000 min
0.1 min
30.0 min
Setting for how long time the short
cooling time constant is used when
the motor is stopped. When motor is
just stopped the cooling typically is
faster in the beginning. May be need
to be adjusted according to
application for perfect match. (This
setting value is visible when “multiple”
time constants is selected).
Short Cool T used when
stop (est)
0.0...3000 min
0.1 min
30.0 min
Estimated setting for how long time
the short cooling time constant is used
when the motor is stopped. When
motor is just stopped the cooling
typically is faster in the beginning.
(This setting value is visible when
“multiple” time constants is selected).
Cold Reset theta default
0.0…150.0%
0.1%
60.0%
Default theta when function is
restarted.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...