Application Guide - NP900 Series
474 (504
)
A996A
Table 3.7.2.5-279. Register content.
Date & Time
Event
code
Volt 1,2,3 status
System status
Input
A,B,C
angle diff
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
3392-
3403
Descr.
0b=No Voltage;
1b=Voltage Ok;
2b=Low Voltage
0=BusDead;
1=BusLive VTSok
SeqOk;
2=BusLive VTSok
SeqRev;
3=BusLive VTSok
SeqUndef;
4=BusLive VTS
fault;
-
-
1 - 8
3.7.3
D
ISTURBANCE RECORDER
(DR)
The disturbance recorder in NP900 IED is a high capacity (60 Mbyte) and fully digital
recorder integrated to protection relay. Maximum sample rate of the recorder analog
channels is 64 samples per cycle. The recorder supports 96 digital channels
simultaneously with measured 9 analog channels.
The recorder provides great tool to analyze the performance of the power system in
network disturbance situations. Recorder output is in general comtrade format and it is
compatible with most viewers and injection devices. Comtrade file is based on standard
IEEE Std C37.111-1999. Captured recordings can be injected as playback with secondary
testing tools those support comtrade file format. Playback of files might help to analyze
the fault or can be simply used in educational purposes.
3.7.3.1
A
NALOG AND DIGITAL RECORDING CHANNELS
NP900 IED supports up to 9 analog recording channels and 96 digital channels
simultaneously. Possible analog channels vary according the IED type. All analog
channels are presented below:
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...