Application Guide - NP900 Series
306 (504
)
A996A
3.4.6.4
O
PERATING TIME CHARACTERISTICS FOR TRIP AND RESET
This function supports definite time delay (DT). For detailed information on this delay type
refer to chapter General properties of a protection function.
3.4.6.5
E
VENTS AND REGISTERS
The SEF function generates events and registers from the status changes of start, trip and
blocked. To main event buffer is possible to select status “On” or “Off” messages. The
SEF function offers four independent instances which events are segregated for each
instance operation.
In the function is available 12 last registers where the triggering event of the function
(start, trip or blocked) is recorded with time stamp and process data values.
Table 3.4.6.5-204. Event codes of the SEF function.
In the register of the SEF function is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of SEF function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.4.6.5-205. Register content.
Date & Time
Event
code
Trigger
Voltage
Fault
voltage
Prefault
voltage
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
6656-
6661
Descr.
Start
average
voltage
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
Alarm
Type
6656
104 SEF1
0 Start ON
1
0
6657
104 SEF1
1 Start OFF
0
0
6658
104 SEF1
2 Trip ON
1
1
6659
104 SEF1
3 Trip OFF
0
0
6660
104 SEF1
4 Block ON
1
0
6661
104 SEF1
5 Block OFF
0
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...