Application Guide - NP900 Series
186 (504
)
A996A
Table 3.2.18.5-127. Event codes of the OPW function.
In the register of the OPW function is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of OPW function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.18.5-128. Register content.
Date & Time
Event
code
Trigger
power
Fault
power
Prefault
power
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
4608-
4613
Descr.
Start
average
power
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
3.2.19
U
NDER POWER
(37)
NP900 series IEDs with both voltage –and current cards can have under power function
(UPW), which is used for instant- and time delayed active under power protection. Under
power function detects loss-of-load conditions when there is no significant loss of current.
Below is presented formula for three phase active power (P) calculation when line-to-
neutral voltages are available:
P
L1
= U
L1
× I
L1
cos
φ
Where,
P
L2
= U
L2
× I
L2
cos
φ
UL1…UL3 = Line to neutral voltage
P
L3
= U
L3
× I
L3
cos
φ
IL1…IL3 = Phase current
P = P
L1
+ P
L2
+ P
L3
φ
= Angle difference between voltage and current
In case the line to line voltages are measured and zero sequence voltage is not measured
and known the three phase power calculation is based on Aaron’s theorem:
P = U
23
× I
L1
cos(30-
φ
) + U
31
× I
L2
cos(30 +
φ
)
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
Alarm
Type
4608
72 OPW1
0 Start ON
1
0
4609
72 OPW1
1 Start OFF
0
0
4610
72 OPW1
2 Trip ON
1
1
4611
72 OPW1
3 Trip OFF
0
0
4612
72 OPW1
4 Block ON
1
0
4613
72 OPW1
5 Block OFF
0
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...