Application Guide - NP900 Series
394 (504
)
A996A
Name
Range
Step
Default
Description
SYN U conditions LL only
LL & LD
LL & DL
LL & DD
LL & LD & DL
LL & LD & DD
LL & DL & DD
Bypass
-
LL only
Allowed states of the supervised systems.
SYN U live >
0.10…120.00 %Un 0.01%Un 20%Un
Voltage limit of the live state
SYN U dead <
0.10…120.00 %Un 0.01%Un 20%Un
Voltage limit of the dead state
SYN U diff <
0.00…120.00 %Un 0.01%Un 2%Un
Maximum allowed voltage difference
between the systems.
SYN angle diff <
0.00…90.00 deg
0.01 deg 0.5 deg
Maximum allowed angle difference
between the systems.
SYN freq diff <
0.00…0.50 Hz
0.01 Hz
0.1 Hz
Maximum allowed frequency difference
between the systems.
NOTE! Remember to set a voltage channel (U3 or U4) into synchrocheck mode in the voltage
transformer settings (Measurements > VT Module).
1.1.1.15
E
VENTS AND REGISTERS
The synchrocheck function generates events and registers from the status changes like
syn ok, bypass and blocked. To main event buffer is possible to select status “On” or “Off”
messages. The synchrocheck function offers three independent instances which events
are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function is
recorded with time stamp and process data values.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...