Application Guide - NP900 Series
309 (504
)
A996A
Table 1.1.1.1-206 Settings of the TRF function.
Name
Range
Step
Default
Funcs.
Description
Transformer
nominal MVA
0.1…
500.0 MVA
0.1MV
A
1.0MVA
All
Nominal MVA of transformer.
This value is used to calculate
nominal currents of HV, and
LV side.
HV side nominal
voltage
0.1…
500.0 kV
0.1kV
110.0kV
All
HV side nominal voltage of the
transformer. This value is used
to calculate nominal currents
of HV side.
LV side nominal
voltage
0.1…
500.0 kV
0.1kV
110.0kV
All
LV side nominal voltage of the
transformer. This value is used
to calculate nominal currents
of LV side.
Transformer Zk%
0.01…
25.00%
0.01%
3.00%
Info
Transformer short circuit
impedance in %. Used for
calculation of the short circuit
currents
Transformer nom.
freq
10…
75Hz
1Hz
50Hz
Info
Transformer nominal
frequency. Used for calculation
of transformer nominal short
circuit inductance.
Transf. Vect.
group
0:Manual
1:Yy0
2:Yyn0
3:YNy0
4:YNyn0
5:Yy6
6:Yyn6
7:YNy6
8:YNyn6
9:Yd1
10:YNd1
11:Yd7
12:YNd7
13:Yd11
14:YNd11
15:Yd5
16:YNd5
17:Dy1
18:Dyn1
19:Dy7
20:Dyn7
21:Dy11
22:Dyn11
23:Dy5
24:Dyn5
25:Dd0
26:Dd6
-
1:Yy0
TRF, DIFF Selection of the transformer
vector group. Selection values
from 1 to 26 are predefined so
that just by selecting correct
vector group the scaling and
vector matching is applied in
the relay automatically.
In the predefinitions it is
assumed that the HV side is
connected to CT1 module and
LV side is in CT2 module.
If the protected transformer
vector group is not found in the
predefined list, manual set can
be applied by selecting 0:
Manual set.
HV side Star or
Zigzag / Delta
0:Star/Zigzag
1:Delta
-
0:Star/Zi
gzag
TRF, DIFF Selection of the HV side
connection, star or zigzag or
delta. Selection is visible only
if vector group is set to
“0:Manual set”
HV side grounded 0:Not
grounded
1:Grounded
-
0:Not
grounded
TRF, DIFF Selection whether the zero
sequence compensation
should be applied into HV side
currents calculation. Selection
is visible only if vector group is
set to “0:Manual set”
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...