Application Guide - NP900 Series
190 (504
)
A996A
UPW function offers four independent instances which events are segregated for each
instance operation.
12 last registers are available in the function where the triggering event of the function
(start, trip or blocked) is recorded with time stamp and process data values.
Table 3.2.19.5-131. Event codes of the UPW function.
In the register of the UPW function is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of UPW function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.19.5-132. Register content.
Date & Time
Event
code
Trigger
power
Fault
power
Prefault
power
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
4672-
4677
Descr.
Start
average
power
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
3.2.20
R
EVERSE POWER
(32R)
NP900 series IEDs with both voltage –and current cards can have reverse power function
(RPW), which is used for instant- and time delayed active reverse power protection. In
generator protection applications reverse power protection function is used to prevent
damage in situations where synchronous generator is running like a motor when the
generator draws active power. Reverse power protection isn’t used to protect the
generator itself but to protect the generators turbine.
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
Alarm
Type
4672
73 UPW1
0 Start ON
1
0
4673
73 UPW1
1 Start OFF
0
0
4674
73 UPW1
2 Trip ON
1
1
4675
73 UPW1
3 Trip OFF
0
0
4676
73 UPW1
4 Block ON
1
0
4677
73 UPW1
5 Block OFF
0
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...