Application Guide - NP900 Series
277 (504
)
A996A
Ist> (48)
Im> (50M)
Hot condition
theta limit
0.0…100.0% 0.1% 70%
MST
N> (48)
TM> (49M)
Ist> (48)
Im> (50M)
Setting of the thermal limit Hot /
Cold situation of the motor. When
this setting value is not exceed and
locked rotor situation occurs cold
stall curve adjusted with actual used
thermal capacity is utilized. After
this setting value hot stall curve is
utilized. Applies also for Starts when
hot / cold selection. NOTE:Usage
requires that the Thermal protection
TM> is activated and in use.
Safe stall time
cold
0.1…600.0s
0.1s
20.0s
MST
TM> (49M)
Ist> (48)
Im> (50M)
N> (48)
Safe stall time when motor is cold. If
this value is not informed then set to
same than hot stall time. This leads
most probably to overprotection with
cold motor stall but is best guess in
such case. This setting value is
used for the cold thermal stall curve
selection in automatic control. Also
motor start-up and number of starts
calculations use this parameter.
Safe stall time
hot
0.1…600.0s
0.1s
15.0s
MST
TM> (49M)
Ist> (48)
Im> (50M)
N> (48)
Safe stall time when motor is hot.
This setting value is used for the hot
thermal stall curve selection in
automatic control. Also motor start-
up and number of starts calculations
use this parameter.
Table 3.3.6.2-179 Pick-up setting
Name
Description
Range
Step
Default
Iset
Pick-up setting
0.10 … 40.00 x In
0.01 x In
0.5 x In
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active.
The operating timers’ behavior of the function can be set for trip signal and also for the
release of the function in case the pick-up element is reset before the trip time has been
reached. There are three basic operating modes available for the function. Instant
operation gives the trip signal with no additional time delay simultaneously with start
signal. Definite time operation (DT) will give trip signal with user given time delay
regardless of the measured current as long as the current is above the Iset value and thus
pick-up element is active (independent time characteristics).
In the following table are presented the setting parameters for the function time
characteristics.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...