Application Guide - NP900 Series
263 (504
)
A996A
TM> (49M)
Ist> (48)
Im> (50M)
this setting value is not exceed and
locked rotor situation occurs cold
stall curve adjusted with actual used
thermal capacity is utilized. After
this setting value hot stall curve is
utilized. Applies also for Starts when
hot / cold selection. NOTE:Usage
requires that the Thermal protection
TM> is activated and in use.
Safe stall time
cold
0.1…600.0s
0.1s
20.0s
MST
TM> (49M)
Ist> (48)
Im> (50M)
N> (48)
Safe stall time when motor is cold. If
this value is not informed then set to
same than hot stall time. This leads
most probably to overprotection with
cold motor stall but is best guess in
such case. This setting value is
used for the cold thermal stall curve
selection in automatic control. Also
motor start-up and number of starts
calculations use this parameter.
Safe stall time
hot
0.1…600.0s
0.1s
15.0s
MST
TM> (49M)
Ist> (48)
Im> (50M)
N> (48)
Safe stall time when motor is hot.
This setting value is used for the hot
thermal stall curve selection in
automatic control. Also motor start-
up and number of starts calculations
use this parameter.
Table 3.3.3.1-164 Settings of the LRC function.
Name
Range
Step
Default
Description
Starting time
0.000…1800.00
0 s
0.005 s 0.040s
User settable motor starting time. This
setting should include the expected normal
starting time of the protected motor
including the operating marginal.
Definite time or
I2t
0:Definite
1:I2t mode
-
0:Definite
Selection of the operating mode. If I2t mode
is selected the function shall monitor the
heating effect in function of the measured
current. In Definite mode the function shall
monitor only the start / stall signal duration
and compare it to user given “Starting time”
setting.
Speed switch in
use
0:No
1:Yes
-
0:No
Selection whether speed switch is used or
not in the application.
Speed SW wait
time
0.000…1800.00
0s
0.005 s 0.040s
Setting which time the speed switch is
waited to give signal from starting of the
motor. If the speed switch is not activating
during this given time the starting of the
motor is halted. This setting is visible only if
“Speed switch in use” setting is “1:Yes”.
Speed SW
NO/NC
0:NO
1:NC
-
0:NO
Polarity of the speed switch signal, normally
open NO or normally closed NC. This
setting is visible only if “Speed switch in
use” setting is “1:Yes”.
Operate mode
0:Starts only
1:Starts and stall
-
0:Starts only Operating mode selection of the LRC
function. This setting defines if the function
monitors only start-up or start-up and stall
conditions of the motor.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...