Application Guide - NP900 Series
495 (504
)
A996A
function and is always related to the setting
value. The setting value is common for all
measured phases and single-, dual- or all phases Im exceed of the Iset value will cause
pick-up operation of the function.
Table 3.7.6.2-290 Pick-up characteristics setting
Name
Range
Step
Default
Description
Enable PH
On
Off
-
Off
Enable of the THD alarm function from
phase currents.
Enable I01
On
Off
-
Off
Enable of the THD alarm function from
residual current input I01.
Enable I02
On
Off
-
Off
Enable of the THD alarm function from
residual current input I02.
IsetPh
0.10 … 200.00 %
0.01 %
20.00 %
Pick-up setting for THD alarm element from
the phase currents. The measured THD
value has to be over this setting on at least
one of the measured phases to activate the
alarm signal.
IsetI01
0.10 … 200.00 %
0.01 %
20.00 %
Pick-up setting for THD alarm element from
the residual current I01. The measured
THD value has to be over this setting to
activate the alarm signal.
IsetI02
0.10 … 200.00 %
0.01 %
20.00 %
Pick-up setting for THD alarm element from
the residual current I02. The measured
THD value has to be over this setting to
activate the alarm signal.
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active.
3.7.6.3
F
UNCTION BLOCKING
In the blocking element the block signal is checked in the beginning of each program
cycle. Blocking signal is received from the blocking matrix for the function dedicated input.
If the blocking signal is not activated when the pick-up element activates, a START signal
is generated and the function proceeds to the time characteristics calculation.
If blocking signal is active when pick-up element activates a BLOCKED signal will be
generated and the function shall not process the situation further. If START function has
been activated before blocking signal it will reset and the release time characteristics are
processed as in case of when pick-up signal is reset.
From blocking of the function a HMI display event as well as time stamped blocking event
with information of the startup current values and fault type is issued.
Blocking signal can be tested also in the commissioning phase of the stage by software
switch signal when relay common and global testing mode is activated.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...