Application Guide - NP900 Series
117 (504
)
A996A
Figure 3.2.9.4-58 Dedicated CBFP operation from binary input signal.
In this mode the CBFP operates from binary input signal only. Additionally also current
and output relay monitoring can be used. The counter for the CBFP is started when the
digital input is activated. If the counter is active until the time in the CBFP counter is used
the IED will issue CBFP command to the incomer breaker. In this application all of the
outgoing feeders IED:s tripping signals can be connected to one dedicated CBFP IED
which operates either on current based or all possible faults CBFP protection.
3.2.9.5
E
VENTS AND REGISTERS
The CBFP function generates events and registers from the status changes of Retrip,
CBFP activated and blocked signals as well as from the internal pick-up comparators. To
main event buffer is possible to select status “On” or “Off” messages.
In the function is available 12 last registers where the triggering event of the function
(Retrip, CBFP activated or blocked) is recorded with time stamp and process data values.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...