Application Guide - NP900 Series
155 (504
)
A996A
Table 3.2.13.6-107. Event codes of the OV function instance 1 – 4.
In the register of the OV function is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of OV function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.13.6-108. Register content.
Date & Time
Event
code
Fault
type
Trigger
voltage
Fault
voltage
Prefault
voltage
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
5440-
5637
Descr.
L1-…
L1-L2-
L3
Start
average
voltage
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
3.2.14
U
NDER VOLTAGE
U<
(27)
Undervoltage function (UV) is used for instant- and time delayed undervoltage protection
for various applications including feeder, filter and machine applications of utilities and
industry. Each IED with voltage protection module has four available instances of the
function (U<, U<<, U<<<, U<<<<). Function measures constantly phase voltage- or line to
line voltage magnitudes. Function measures constantly phase voltage magnitudes or line-
to line voltage magnitudes. Undervoltage protection is based to line- to line fundamental
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
5440
85 OV1
0 Start ON
1
5441
85 OV1
1 Start OFF
0
5442
85 OV1
2 Trip ON
1
5443
85 OV1
3 Trip OFF
0
5444
85 OV1
4 Block ON
1
5445
85 OV1
5 Block OFF
0
5504
86 OV2
0 Start ON
1
5505
86 OV2
1 Start OFF
0
5506
86 OV2
2 Trip ON
1
5507
86 OV2
3 Trip OFF
0
5508
86 OV2
4 Block ON
1
5509
86 OV2
5 Block OFF
0
5568
87 OV3
0 Start ON
1
5569
87 OV3
1 Start OFF
0
5570
87 OV3
2 Trip ON
1
5571
87 OV3
3 Trip OFF
0
5572
87 OV3
4 Block ON
1
5573
87 OV3
5 Block OFF
0
5632
88 OV4
0 Start ON
1
5633
88 OV4
1 Start OFF
0
5634
88 OV4
2 Trip ON
1
5635
88 OV4
3 Trip OFF
0
5636
88 OV4
4 Block ON
1
5637
88 OV4
5 Block OFF
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...