Application Guide - NP900 Series
353 (504
)
A996A
Table 1.1.1.10-213 Settings related to DIF function pre calculation. (continued).
Name
Range
Step
Default
Funcs.
Description
Enable I0d>
(REF) LV side
0:Disabled
1:Enabled
-
0: Disabled TRF,DIFF
LV side restricted earth fault
stage enable/disable selection.
LV side Starpoint
meas,
0:I01
1:I02
-
0:I01
TRF,DIFF
Selection of the starpoint
measurement channel for the
LV side restricted earth fault
protection. Setting is visible
only if “Enable I0d> (REF) LV
side” is set to “1: Enabled”
Table 1.1.1.10-214 DIF function operating characteristics settings.
Name
Range
Step
Default
Description
Differential
calculation mode
0: Add
1:Subtract
-
1:Subtract
Calculation mode of the differential
current. Depends of the installation
direction of the CT:s and the desired
current directions. If both sides current
flow same direction differential current is
subtracted, if opposite then added.
Bias calculation
mode
0: Average
1:Maximum
-
0:Average
Calculation mode of biasing current. With
average mode the operation may be set
more sensitive while maximum mode the
bias will be always higher thus giving
more stable operation.
Idb> Pickup
0.01…100.00%
0.01%
10.00%
Base sensitivity for the differential
characteristics
Turnpoint 1
0.01…50.00xIn
0.01xIn 1.00xIn
Turnpoint 1 for the differential
characteristics
Slope 1
0.01…250.00%
0.01%
10.00%
Slope1 of the differential characteristics
Turnpoint2
0.01…50.00xIn
0.01xIn 3.00xIn
Turnpoint 2 for the differential
characteristics
Slope 2
0.01…250.00%
0.01%
200.00%
Slope2 of the differential characteristics
Enable harmonic
blocking
0: No harm.block
1: 2
nd
harm block
2: 5
th
harm block
3: 2
nd
and 5
th
harm
block
-
1: 2
nd
harm
block
Selection of the internal blockings to be
used for detection of transformer normal
but differential current causing
operations.
2
nd
harm block
pickup
0.01…50.00%
0.01%
15.00%
Pick-up detection relation (fundamental
to harmonic ratio) for 2
nd
harmonic
blocking stage. This setting is visible only
if the “Enable harmonic blocking” setting
is set either to 1 or 3 mode.
5
th
harm block
pickup
0.01…50.00%
0.01%
35.00%
Pick-up detection relation (fundamental
to harmonic ratio) for 5
th
harmonic
blocking stage. This setting is visible only
if the “Enable harmonic blocking” setting
is set either to 2 or 3 mode.
Enable Idi> stage
0: Disabled
1: Enabled
-
1:Enabled
Selection of the non biased and non
blocked differential stage enabled or
disabled.
Idi> No bias Pickup 200.00…1500.00%
0.01%
600.00%
Pick-up setting for the non biased/non
blocked differential stage. This setting is
visible only if “Enable Idi>” stage is set to
1.
HV I0d> Pickup
0.01…100.00%
0.01%
10.00%
Base sensitivity for the HV side restricted
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...