Application Guide - NP900 Series
324 (504
)
A996A
Figure 1.1.1.5-156 Natural differential current sources.
Differential current sources in normal operation:
-
Primary side CT measurement accuracy (CTE pri)
-
Secondary side CT measurement accuracy (CTE sec)
-
Relay measurement accuracy (primary and secondary) (REm)
-
Tap changer on load side (TCE)
-
Possible auxiliary transformer or auxiliary winding, which currents are not measured
separately (AUTE)
-
Transformer core magnetizing current (TME)
-
Safety margin (SME)
Now how to get the base sensitivity setting limit
I
d>Pick
-
up
, errors have to be calculated
part by part.
CTEpri: In this example case primary side CT:s are class 10P which means 10% of
measurement error.
CTEsec: In this example case secondary side CT:s are class 5P which means 5% of
measurement error.