Application Guide - NP900 Series
489 (504
)
A996A
Table 3.7.5.2-285 Circuit breaker characteristics settings.
Name
Range
Step
Default
Description
Current 1
(Inom)
0.00…100.00 kA
0.01 kA
1.00 kA
Nominal operating current of the breaker
(rms)
Operations
(Inom)
0… 200000 Op
1 Op
50000 Op Interrupting life operations at rated current
(Close - Open)
Current 2
(Imax)
0.00…100.00 kA
0.01 kA
20.00 kA Rated short circuit breaking current (rms)
Operations
(Imax)
0… 200000 Op
1 Op
100 Op
Interrupting life operations at rated breaking
current (Open)
3.7.5.3
P
ICK
-
UP CHARACTERISTICS FOR ALARM
For the alarm stages Alarm 1 and Alarm 2 can be set pick-up level for the remaining
operations left. The pick-up setting is common for all phases and the alarm stage shall
pick-up if any of the phases is below this setting.
Table 3.7.5.3-286 Pick-up characteristics setting
Name
Range
Step
Default
Description
Enable
Alarm 1
0: Disabled
1: Enabled
-
Enabled
Enable / Disable selection of the Alarm 1
stage
Alarm 1 Set
0 … 200000
operations
1 operation
1000 op
Pick-up threshold for remaining operations.
When the remaining operations is below
this setting Alarm 1 signal is activated.
Enable
Alarm 2
0: Disabled
1: Enabled
-
Enabled
Enable / Disable selection of the Alarm 2
stage
Alarm 2 Set
0 … 200000
operations
1 operation
100 op
Pick-up threshold for remaining operations.
When the remaining operations is below
this setting Alarm 2 signal is activated.
3.7.5.4
F
UNCTION BLOCKING
For this function are no separate blocking procedures available. The function can be
either enabled or disabled and the Alarm 1 or Alarm 2 stages can be enabled or disabled.
3.7.5.5
E
VENTS AND REGISTERS
The CBW function generates events and registers from the status changes of Retrip,
CBW activated and blocked signals as well as from the internal pick-up comparators. To
main event buffer is possible to select status “On” or “Off” messages.
In the function is available 12 last registers where the triggering event of the function is
recorded with time stamp and process data values.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...