Table 3.1.1.5-9 Per unit residual current measurements in NP900.
Name
Range
Step
Description
Residual current I01
0.00…1250.0 xIn
0.01xIn
Per unit measurement from residual
current channel I01 fundamental
frequency RMS current.
Residual current I02
0.00…1250.0 xIn
0.01xIn
Per unit measurement from residual
current channel I02 fundamental
frequency RMS current.
Calculated I0
0.00…1250.0 xIn
0.01xIn
Per unit measurement from calculated I0
current fundamental frequency RMS
current.
Phase current I01 TRMS
0.00…1250.0 xIn
0.01xIn
Per unit measurement from I01 residual
current channel TRMS current including
harmonics up to 31
st
.
Phase current I02 TRMS
0.00…1250.0 xIn
0.01xIn
Per unit measurement from I02 residual
current channel TRMS current including
harmonics up to 31
st
.
Peak to peak current I01
0.00…500.0 xIn
0.01xIn
Per unit measurement peak to peak
current from I01 residual current
measurement channel.
Peak to peak current I02
0.00…500.0 xIn
0.01xIn
Per unit measurement peak to peak
current from I02 residual current
measurement channel.
Table 3.1.1.5-10 Primary residual current measurements in NP900.
Name
Range
Step
Description
Primary residual current
I01
0.00…1000000.0A
0.01A
Primary measurement from residual
current channel I01 fundamental
frequency RMS current.
Primary residual current
I02
0.00…1000000.0A
0.01A
Primary measurement from residual
current channel I02 fundamental
frequency RMS current.
Primary calculated I0
0.00…1000000.0A
0.01A
Primary measurement from calculated I0
fundamental frequency RMS current.
Residual current I01
TRMS pri
0.00…1000000.0A
0.01A
Primary measurement from residual
current channel I01 TRMS current
including harmonics up to 31
st
.
Residual current I02
TRMS pri
0.00…1000000.0A
0.01A
Primary measurement from residual
current channel I02 TRMS current
including harmonics up to 31
st
.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...