Application Guide - NP900 Series
301 (504
)
A996A
Resetting characteristics can be set according to the application. Default setting is
delayed with 60 ms and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the
operating time during the release time, function will not trip if the input signal is not
activated again during the release time counting.
3.4.5.3
F
UNCTION BLOCKING
In the blocking element the block signal is checked in the beginning of each program
cycle. Blocking signal is received from the blocking matrix for the function dedicated input.
If the blocking signal is not activated when the pick-up element activates, a START signal
is generated and the function proceeds to the time characteristics calculation.
If blocking signal is active when pick-up element activates a BLOCKED signal will be
generated and the function shall not process the situation further. If START function has
been activated before blocking signal it will reset and the release time characteristics are
processed as in case of when pick-up signal is reset.
From blocking of the function a HMI display event as well as time stamped blocking event
with information of the startup voltage values and fault type is issued.
Blocking signal can be tested also in the commissioning phase of the stage by software
switch signal when relay common and global testing mode is activated.
User settable variables are binary signals from the system. Blocking signal needs to reach
the IED minimum of 5 ms before the set operating delay has passed for blocking to be
active in time.
3.4.5.4
E
VENTS AND REGISTERS
The V/Hz function generates events and registers from the status changes of start, trip
and blocked. To main event buffer is possible to select status “On” or “Off” messages. The
V/Hz function offers one stage which can be set to definite or/and inverse operating time
characteristics.
In the function is available 12 last registers where the triggering event of the function
(start, trip or blocked) is recorded with time stamp and process data values.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...