Application Guide - NP900 Series
136 (504
)
A996A
Now when trying to load the
cable with the given nominal
current can be seen that the
actual cable current carrying
capacity is much lower than in
presumption conditions. Normal
loading current can now get the
cable too warm and endanger
its withstandability. If in this
case the k
SF
factor would not
been set the thermal image
would show about 68
̊
C
temperature when it in reality
would be 96
̊
C.
Figure 3.2.11-75 Thermal image response with nominal currents and fine tuned k
SF
correction factor.
When the installation conditions
vary from the presumption
conditions like in this example,
the current carrying capacity of
the cable had been reduced so
that 90
̊
C temperature is
achieved already with 550A
current instead of the initial data
given current of 680A.
Figure 3.2.11-76 Thermal response with k
SF
factor correctly set.