Application Guide - NP900 Series
371 (504
)
A996A
Table 3.6.1.1-232. Signals of the SGS function
Name
Range
Step
Default
Description
Setting group 1
0=Not active
1=Active
1
0
Setting group 1 selection, highest priority
input for setting group control. Can be
controlled with pulse or steady state
signals. If steady state signal is applied no
other SG requests shall be processed.
Setting group 2
0=Not active
1=Active
1
0
Setting group 2 selection, second highest
priority input for setting group control. Can
be controlled with pulse or steady state
signals. If steady state signal is applied no
lower priority than SG1 requests shall be
processed.
Setting group 3
0=Not active
1=Active
1
0
Setting group 3 selection, third highest
priority input for setting group control. Can
be controlled with pulse or steady state
signals. If steady state signal is applied no
lower priority than SG1 and SG2 requests
shall be processed.
Setting group 4
0=Not active
1=Active
1
0
Setting group 4 selection, fourth highest
priority input for setting group control. Can
be controlled with pulse or steady state
signals. If steady state signal is applied no
lower priority than SG1,SG2 and SG3
requests shall be processed.
Setting group 5
0=Not active
1=Active
1
0
Setting group 6 selection, fourth lowest
priority input for setting group control. Can
be controlled with pulse or steady state
signals. If steady state signal is applied
SG6, SG7 and SG8 requests shall not be
processed.
Setting group 6
0=Not active
1=Active
1
0
Setting group 6 selection, third lowest
priority input for setting group control. Can
be controlled with pulse or steady state
signals. If steady state signal is applied
SG7 and SG8 requests shall not be
processed.
Setting group 7
0=Not active
1=Active
1
0
Setting group 7 selection, second lowest
priority input for setting group control. Can
be controlled with pulse or steady state
signals. If steady state signal is applied only
SG8 requests shall not be processed.
Setting group 8
0=Not active
1=Active
1
0
Setting group 8 selection, lowest priority
input for setting group control. Can be
controlled with pulse or steady state
signals. If steady state signal is applied all
other SG requests shall be processed no
matter of this signal status.
Active SG
0…7
1
0
Active SG at the moment. This output
signal is used by all other functions.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...