Application Guide - NP900 Series
278 (504
)
A996A
Table 3.3.6.2-180 Operating time characteristics setting parameters.
Name
Range
Step
Default
Description
Definite operating
time delay
0.000…1800.000 s 0.005 s
0.040 s
Definite time operating delay. Setting is
active and visible when Delay Type is
selected to DT.
When set to 0.000 s the stage operates as
instant (PIOC, 50) stage without added
delay. When the parameter is set to 0.005
– 1800 s the stage operates as
independent delayed (PTOC, 51).
Table 3.3.6.2-181 Reset time characteristics setting parameters.
Release Time
delay
0.000…150.000 s
0.005 s
0.06 s
Resetting time. Time allowed in between
of pick-ups if the pick-up has not lead into
trip operation. During this time the start
signal is held on for the timers if delayed
pick-up release is active.
Delayed Pick-up
release
No
Yes
-
Yes
Resetting characteristics selection either
time delayed or instant after pick-up
element is released. If activated the start
signal is reset after set release time delay.
Time calc reset
after release time
No
Yes
-
Yes
Operating timer resetting characteristics
selection. When active the operating time
counter is reset after set release time if
pick-up element is not activated during this
time. When disabled the operating time
counter is reset directly after the pick-up
element reset.
Continue time
calculation during
release time
No
Yes
-
No
Time calculation characteristics selection.
If activated the operating time counter is
continuing until set release time even the
pick-up element is reset.
Resetting characteristics can be set according to the application. Default setting is
delayed with 60 ms and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the
operating time during the release time, function will not trip if the input signal is not
activated again during the release time counting.
3.3.6.3
F
UNCTION BLOCKING
In the blocking element the block signal is checked in the beginning of each program
cycle. Blocking signal is received from the blocking matrix for the function dedicated input.
If the blocking signal is not activated when the pick-up element activates, a START signal
is generated and the function proceeds to the time characteristics calculation.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...