Application Guide - NP900 Series
30 (504
)
Table 3.1.2.4-27 Primary voltage measurements in NP900.
Name
Range
Step
Description
System volt UL12 mag
0.00…1000000.00V 0.01V
Primary measured or calculated
fundamental frequency RMS line to line
UL12 voltage.
System volt UL23 mag
0.00…1000000.00V 0.01V
Primary measured or calculated
fundamental frequency RMS line to line
UL23 voltage.
System volt UL31 mag
0.00…1000000.00V 0.01V
Primary measured or calculated
fundamental frequency RMS line to line
UL31 voltage.
System volt UL1 mag
0.00…1000000.00V 0.01V
Primary measured or calculated
fundamental frequency RMS line to
neutral UL1 voltage.
System volt UL2 mag
0.00…1000000.00V 0.01V
Primary measured or calculated
fundamental frequency RMS line to
neutral UL2 voltage.
System volt UL3 mag
0.00…1000000.00V 0.01V
Primary measured or calculated
fundamental frequency RMS line to
neutral UL3 voltage.
System volt U0 mag
0.00…1000000.00V 0.01V
Primary measured or calculated
fundamental frequency RMS zero
sequence U0 voltage.
System volt U3 mag
0.00…1000000.00V 0.01V
Primary measured fundamental frequency
RMS Synchro-check SS voltage. (Valid
only in 2LL+U3+U4 mode)
System volt U4 mag
0.00…1000000.00V 0.01V
Primary measured fundamental frequency
RMS Synchro-check SS voltage.
Table 3.1.2.4-28 Primary voltage angles in NP900.
Name
Range
Step
Description
System volt UL12 ang
0.00…360.0deg
0.01deg Primary measured or calculated line to
line UL12 angle.
System volt UL23 ang
0.00…360.0deg
0.01deg Primary measured or calculated line to
line UL23 angle.
System volt UL31 ang
0.00…360.0deg
0.01deg Primary measured or calculated line to
line UL31 angle.
System volt UL1 ang
0.00…360.0deg
0.01deg Primary measured or calculated line to
neutral UL1 angle.
System volt UL2 ang
0.00…360.0deg
0.01deg Primary measured or calculated line to
neutral UL2 angle.
System volt UL3 ang
0.00…360.0deg
0.01deg Primary measured or calculated line to
neutral UL3 angle.
System volt U0 ang
0.00…360.0deg
0.01deg Primary measured or calculated zero
sequence U0 angle.
System volt U3 ang
0.00…360.0deg
0.01deg Primary measured Synchro-check SS
angle. (Valid only in 2LL+U3+U4 mode)
System volt U4 ang
0.00…360.0deg
0.01deg Primary measured Synchro-check SS
angle.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...