Application Guide - NP900 Series
22 (504
)
Figure 3.1.2.1-13 Example connection with three line to neutral voltages and zero
sequence voltage connected. 3LN+U4 mode has to be selected. U4 channel has to be set
as U0.
Initial data of the connection and the ratings are presented in following table.
Table 3.1.2.1-18 Initial data of previous example connection.
Phase voltage VT:
VT primary 20000V
VT secondary 100V
Zero sequence voltage VT:
U4 VT primary 20000V
U4 VT secondary 100V
Zero sequence voltage is connected similar way with Line to neutral voltages
(+U0).
In case of incorrect wiring all polarities can be switched individually by 180
degrees in IED.
If voltage based protection is used the supervised voltage may be based on line to line –or
line to earth voltages. This selection is completed in each protection stage menu
separately.
Voltage protection is based on nominal voltage. If 20000V is set to be the nominal voltage
this equals 100% setting in voltage based protection functions. 120% trip setting in
overvoltage stage equals to 24000V on primary level so 20% increase in this case would
be 4000V.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...