Application Guide - NP900 Series
456 (504
)
A996A
3.6.7.5
T
AP SETTINGS
In tap settings the tap changer equipment properties and connection for position indication
to AVR are set.
Table 3.6.7.5-263 Tap settings parameters.
Name
Description
Range
Step
Default
Tap position indication
Selection of tap
position indication
message
0: mA input
1: BCD
2: Resistor net
-
0:mA input
Tap steps totally
Number of tap
steps from
minimum to
maximum
1…70
1
18
Tap center location
Position of nominal
non regulated tap
location
1…35
1
9
Tap step effect
Effect of one tap
step in percentage
of nominal voltage
0.01…10.00%
0.01%
1.67%
mA input low range
mA input
measurement
presenting the
minimum tap
position
0.000…4.000 mA
0.001mA
4.000mA
mA input high range
mA input
measurement
presenting the
maximum tap
position
0.010…20.000 mA
0.001mA
4.000mA
Table 3.6.7.5-264 Tap settings indications and measurements
Name
Description
Range
Step
Default
Tap step voltage effect
One tap step effect
to primary voltage
0.00…5000.00Vpri
0.01Vpri
0 Vpri
Tap maximum
decrease
Maximum voltage
decrease from
nominal position in
percentage
-140.00…0.00%
0.01%
0.00%
Tap maximum increase Maximum voltage
increase from
nominal position in
percentage
0.00…140.00%
0.01%
0.00%
Tap controlband
Tap changer
control band where
the secondary
voltage may be
varied
0.00…140.00%
0.01%
0.00%
Tap step in mA
One tap step effect
change to mA
measurement
0.000…20.000mA
0.001mA
0mA
mA input now
mA input
measurement
value at the
moment
0.000…20.000mA
0.001mA
0mA
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...