Application Guide - NP900 Series
120 (504
)
A996A
3.2.10.1
M
EASURED INPUT VALUES
Function block uses analog current measurement values. Function uses the fundamental
frequency magnitude of the current measurement inputs and calculated residual current
with residual current measurement. For residual current measurement I01 or I02 can be
selected.
Table 3.2.10.1-85 Analogic magnitudes used by the REF function.
Signal
Description
Time base
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
I01RMS
Fundamental RMS measurement of residual input I01
5 ms
I02RMS
Fundamental RMS measurement of residual input I02
5 ms
IL1Ang
Fundamental angle of phase L1/A current
5 ms
IL2 Ang
Fundamental angle of phase L2/B current
5 ms
IL3 Ang
Fundamental angle of phase L3/C current
5 ms
I01 Ang
Fundamental angle of residual input I01
5 ms
I02 Ang
Fundamental angle of residual input I02
5 ms
Selection of the used residual current input AI channel is made with a setting parameter.
Table 3.2.10.1-86 General settings of the REF stage (not SG selectable)
Name
Range
Step
Default
Description
I0d> mode
0: Disabled
1: Activated
-
Disabled
Selection of the function is activated or
disabled in the configuration. Default setting
0: Disabled (Not in use).
REF or Cable
end Diff
0: REF
1: CED
-
REF
Selection of the operating characteristics. If
selected REF the function operates with
normal accuracies and if selected CED the
natural unbalance created by the phase
current CT:s can be compensated for more
sensitive operation. Default setting is REF.
Comp. natural
unbal.
0:-
1:Comp
-
-
When activated in on line the currently
present calculated residual current will be
compensated to 0. This compensation does
not have effect otherwise than in CED
mode.
3.2.10.2
O
PERATING CHARACTERISTICS
Current dependent pick-up and activation of the REF function is controlled by
setting
parameters, which defines the used current calculating method and operating
characteristics.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...