Application Guide - NP900 Series
19 (504
)
Table 3.1.1.5-11 Secondary residual current measurements in NP900.
Name
Range
Step
Description
Secondary residual
current I01
0.00…300.0A
0.01A
Secondary measurement from residual
current channel I01 fundamental
frequency RMS current.
Secondary residual
current I02
0.00…300.0A
0.01A
Secondary measurement from residual
current channel I02 fundamental
frequency RMS current.
Secondary calculated I0
0.00…300.0A
0.01A
Secondary measurement from calculated
I0 fundamental frequency RMS current.
Residual current I01
TRMS sec
0.00…300.0A
0.01A
Secondary measurement from residual
current channel I01 TRMS current
including harmonics up to 31
st
.
Residual current I02
TRMS sec
0.00…300.0A
0.01A
Secondary measurement from residual
current channel I02 TRMS current
including harmonics up to 31
st
.
Table 3.1.1.5-12 Residual current angles measurements in NP900.
Name
Range
Step
Description
Residual current angle
I01
0.00…360.00 deg
0.01deg Residual current angle measurement of
the I01 current input.
Residual current angle
I02
0.00…360.00 deg
0.01deg Residual current angle measurement of
the I02 current input.
Calculated I0 phase
angle
0.00…360.00 deg
0.01deg Calculated residual current angle
measurement.
Table 3.1.1.5-13 Per unit sequence current measurements in NP900.
Name
Range
Step
Description
Positive sequence
current
0.00…1250.0 xIn
0.01xIn
Per unit measurement from calculated
positive sequence current
Negative sequence
current
0.00…1250.0 xIn
0.01xIn
Per unit measurement from calculated
negative sequence current
Zero sequence current
0.00…1250.0 xIn
0.01xIn
Per unit measurement from calculated
zero sequence current
Table 3.1.1.5-14 Primary sequence current measurements in NP900.
Name
Range
Step
Description
Primary Positive
sequence current
0.00…1000000.0A
0.01A
Primary measurement from calculated
positive sequence current
Primary Negative
sequence current
0.00…1000000.0A
0.01A
Primary measurement from calculated
negative sequence current
Primary Zero sequence
current
0.00…1000000.0A
0.01A
Primary measurement from calculated
zero sequence current
Table 3.1.1.5-15 Secondary sequence current measurements in NP900.
Name
Range
Step
Description
Secondary Positive
sequence current
0.00…300.0A
0.01A
Secondary measurement from calculated
positive sequence current
Secondary Negative
sequence current
0.00…300.0A
0.01A
Secondary measurement from calculated
negative sequence current
Secondary Zero
sequence current
0.00…300.0A
0.01A
Secondary measurement from calculated
zero sequence current
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...