Application Guide - NP900 Series
163 (504
)
A996A
Inputs for the function are the available stages, setting parameters and measured and
pre-processed voltage magnitudes and binary input signals. Function outputs ALARM,
TRIP and BLOCKED signals can be used for direct IO controlling and also for user logic
programming. The function registers its operation into 12 last time-stamped registers and
also generates general time stamped ON/OFF events to the common event buffer from
each of the three output signals. When tripping, the function outputs ALARM and TRIP
events simultaneously with equivalent time stamp. Time stamp resolution is 1ms. Function
provides also cumulative counters for ALARM, TRIP and BLOCKED events.
In the following figure is presented the simplified function block diagram of the VJP
function.
Figure 3.2.15-82 Simplified function block diagram of the VJP function.
3.2.15.1
M
EASURED INPUT VALUES
Analog voltage measurement values are used for the function block. Function block
utilizes always complex measurement from samples. For the pre-fault data registering, -20
ms averaged value of the selected magnitude is used.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...