Application Guide - NP900 Series
294 (504
)
A996A
whole harmonic specter of 32 components or peak to peak values. For the pre-fault data
registering -20 ms averaged value of the selected magnitude is used.
Table 3.4.4.1-193 Measurement magnitudes used by the VOC function.
Signal
Description
Time base
IL1PP
Peak-to-peak measurement of phase L1/A current
5 ms
IL2PP
Peak-to-peak measurement of phase L2/B current
5 ms
IL3PP
Peak-to-peak measurement of phase L3/C current
5 ms
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
IL1TRMS
TRMS measurement of phase L1/A current
5 ms
IL2TRMS
TRMS measurement of phase L2/B current
5 ms
IL3TRMS
TRMS measurement of phase L3/C current
5 ms
U1
Positive sequence voltage
5 ms
3.4.4.2
P
ICK
-
UP CHARACTERISTICS
Pick-up level of the VOC function is controlled by setting parameters Iv1, Iv2, Ux1, Ux2
and positive sequence voltage measurement. Pick-up level defines the maximum allowed
measured current before action from the function. The function constantly calculates the
ratio in between of the current pick-up level and measured magnitude (Im) per all three
stages. Reset ratio of 97 % is inbuilt in the function and is always related to the current
pick-up
value.
Table 3.4.4.2-194 Pick-up characteristics setting
Name
Description
Range
Step
Default
Iv1>
1st knee point Iv1>
0.10…40.00 xIn
0.01 xIn
0.6 xIn
Iv2>
2nd knee point Iv2>
0.10…40.00 xIn
0.01 xIn
2.0 xIn
Ux1
1st knee point voltage
0.00…150.00 xUn
0.01 xUn
30%Un
Ux2
2nd knee point voltage
0.00…150.00 xUn
0.01 xUn
80 %Un
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...