Application Guide - NP900 Series
356 (504
)
A996A
1.1.1.11
E
VENTS
DIF function generates events from internal status changes. From changes of the tripping
events also data register is available.
Table 1.1.1.11-217. Event codes of the DIF function.
Table 1.1.1.11-218 Event codes of the DIF function (continued).
Event
Number
Event
channel
Event block name
Event
Code
Description
4544
71 DIF1
0 Idb> Trip On
4545
71 DIF1
1 Idb> Trip Off
4546
71 DIF1
2 Idb> Blocked (ext) On
4547
71 DIF1
3 Idb> Blocked (ext) Off
4548
71 DIF1
4 Idi> Trip On
4549
71 DIF1
5 Idi> Trip Off
4550
71 DIF1
6 Idi> Blocked (ext) On
4551
71 DIF1
7 Idi> Blocked (ext) Off
4552
71 DIF1
8 2.nd Harmonic Block On
4553
71 DIF1
9 2.nd Harmonic Block Off
4554
71 DIF1
10 5.th Harmonic Block On
4555
71 DIF1
11 5.th Harmonic Block Off
4556
71 DIF1
12 HV I0d> Block On
4557
71 DIF1
13 HV I0d> Block Off
4558
71 DIF1
14 HV I0d> Trip On
4559
71 DIF1
15 HV I0d> Trip Off
4560
71 DIF1
16 LV I0d> Block On
4561
71 DIF1
17 LV I0d> Block Off
4562
71 DIF1
18 LV I0d> Trip On
4563
71 DIF1
19 LV I0d> Trip Off
4564
71 DIF1
20 L1Diff On
4565
71 DIF1
21 L1Diff Off
4566
71 DIF1
22 L2Diff On
4567
71 DIF1
23 L2Diff Off
4568
71 DIF1
24 L3Diff On
4569
71 DIF1
25 L3Diff Off
4570
71 DIF1
26 Unrest Diff On
4571
71 DIF1
27 Unrest Diff Off
4572
71 DIF1
28 L1 2.nd harm On
4573
71 DIF1
29 L1 2.nd harm Off
4574
71 DIF1
30 L2 2.nd harm On
4575
71 DIF1
31 L2 2.nd harm Off
4576
71 DIF1
32 L3 2.nd harm On
4577
71 DIF1
33 L3 2.nd harm Off
4578
71 DIF1
34 L1 5.th harm On
4579
71 DIF1
35 L1 5.th harm Off
4580
71 DIF1
36 L2 5.th harm On
4581
71 DIF1
37 L2 5.th harm Off
4582
71 DIF1
38 L3 5.th harm On
4583
71 DIF1
39 L3 5.th harm Off
4584
71 DIF1
40 L1 Harm block On
4585
71 DIF1
41 L1 Harm block Off
4586
71 DIF1
42 L2 Harm block On
4587
71 DIF1
43 L2 Harm block Off
4588
71 DIF1
44 L3 Harm block On
4589
71 DIF1
45 L3 Harm block Off
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...