Application Guide - NP900 Series
449 (504
)
A996A
Figure 3.6.7.1-215 Combined operating time characteristics of voltage windows in
function of voltage deviation to the set target voltage.
From the operating characteristics it can be seen that the faster inverse operation until the
U>>/<< window threshold setting which after U>/< window threshold gives definite
operating time.
Settings for this example are:
U>/< pick-up = (1.2 * TAPEFF) / 2 = (1.2 * 1.67%) / 2 = 1%, Operating time 60 seconds.
U>>/<< pick-up = U>/< pick-up + TAPEFF = 1 % + 1.67% = 2.67%, Operating time 60
seconds.