Voltage transformer supervision is used to detect errors in the secondary circuit of the
voltage transformer. This signal is mostly used as alarming function or to disable functions
that require adequate voltage measurement.
3.7.2.1
M
EASURED INPUT VALUES
The function block uses analog voltage measurement values. Function uses the
fundamental frequency magnitude of the voltage measurement inputs and calculated
positive-, negative- and zero sequence currents.
Table 3.7.2.1-276 Analogic magnitudes used by the VTS function.
Signal
Description
Time base
U
L12
RMS
Fundamental RMS measurement of voltage U
L12
/V
5 ms
U
L23
RMS
Fundamental RMS measurement of voltage U
L23
/V
5 ms
U
L31
RMS
Fundamental RMS measurement of voltage U
L31
/V
5 ms
U
L1
RMS
Fundamental RMS measurement of voltage U
L1
/V
5 ms
U
L2
RMS
Fundamental RMS measurement of voltage U
L2
/V
5 ms
U
L3
RMS
Fundamental RMS measurement of voltage U
L3
/V
5 ms
U1P
Positive sequence voltage
5 ms
U2N
Negative sequence voltage
5 ms
UZ0
Zero sequence voltage
5 ms
U
L12
Ang
Fundamental angle of U
L12
voltage
5 ms
U
L23
Ang
Fundamental angle of U
L23
voltage
5 ms
U
L31
Ang
Fundamental angle of U
L31
voltage
5 ms
U
L1
Ang
Fundamental angle of U
L1
voltage
5 ms
U
L2
Ang
Fundamental angle of U
L2
voltage
5 ms
U
L3
Ang
Fundamental angle of U
L3
voltage
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input
channel variations pre-fault condition is presented with 20 ms averaged history value from
-20 ms of Start or Trip event.
3.7.2.2
P
ICK
-
UP CHARACTERISTICS
Voltage dependent pick-up and activation of the VTS function is controlled by Voltage low
pick-up and Voltage high detect
setting parameters. If at least one measured voltage of
the three are under the set low value, VTS pick-up will activate. Also if at least two of the
three voltages are over high detect value VTS pick-up will activate. The function
constantly calculates the ratio in between of the setting values and measured magnitude
per all three phases and selected residual current input.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...