Application Guide - NP900 Series
145 (504
)
A996A
conditions are met. This feature can be enabled or disabled in the protection functions
settings menu.
Activation and deactivation of this stage can be done inside the protection functions
menus info-tab.
Outputs of the function are Trip and Blocked signals. Setting parameters are static inputs
for the function which are changed only by user input in the setup phase of the function.
Arc protection utilizes total of eight separate setting groups which can be selected from
one common source.
Table 3.2.12-100 Output signals of the arc protection function
Outputs
Channel1 Light In
Channel2 Light In
Channel3 Light In
Channel4 Light In
Channel1 Pressure In
Channel2 Pressure In
Channel3 Pressure In
Channel4 Pressure In
ARC Binary input signal
I/I0 Arc> Ph.Curr.START
I/I0 Arc> Res.Curr.START
I/I0 Arc> Ph.Curr.BLOCKED
I/I0 Arc> Res.Curr.BLOCKED
I/I0 Arc> Zone1 TRIP
I/I0 Arc> Zone1 BLOCKED
I/I0 Arc> Zone2 TRIP
I/I0 Arc> Zone2 BLOCKED
I/I0 Arc> Zone3 TRIP
I/I0 Arc> Zone3 BLOCKED
I/I0 Arc> Zone4 TRIP
I/I0 Arc> Zone4 BLOCKED
The operational logic consists of input processing, threshold comparator, two block signal
check and output processing.
Inputs for the function are the operating mode selections, setting parameters and
measured and pre-processed power magnitudes and binary input signals. Function
outputs TRIP, BLOCKED, light sensing etc. signals can be used for direct IO controlling
and also for user logic programming. The function registers its operation into 12 last time-
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...